SVC-T04 · POWER SYSTEM PROTECTION ENGINEERING

Protection Relay Testing Services in Pakistan.

TransfoLine provides precision Protection Relay Testing & Commissioning for industrial substations, captive power plants, and grid stations across Pakistan. Using industry-standard OMICRON CMC 256 and Megger 3-phase secondary injection test sets, our protection engineers calibrate, verify, and validate numerical, static, and electromechanical protective relays to guarantee fail-safe fault clearance and zero nuisance tripping.

OMICRON CMC TEST SETS ALL RELAY MAKES TRIP CIRCUIT CHECK IEC 60255 COMPLIANT
Secondary injection protection relay testing in Lahore Pakistan
TEST SET CALIBRATION
OMICRON CMC
TIMING ACCURACY
±1 ms
REPORT DELIVERY
24 Hours
01
  EXECUTIVE SUMMARY

What is Protection Relay Testing?

Protection relay testing is the precision testing of electrical protective relays by injecting simulated fault currents and system voltages to confirm that the relay correctly detects electrical faults (overcurrent, short-circuit, earth fault, reverse power, or differential unbalance) and signals the circuit breaker to trip within exact millisecond tolerances.

01

Secondary Injection Testing

Using 3-phase OMICRON CMC test sets, we inject calibrated currents and phase-shifted voltages directly into relay inputs to verify pickup thresholds, dropout ratios, reset times, and inverse definite minimum time (IDMT) operating curves.

02

Scheme & Trip Circuit Validation

We test the end-to-end trip scheme—from relay output contact actuation, through auxiliary tripping relays (Master Trip 86), up to the circuit breaker trip coil to ensure 100% reliable physical breaker opening.

02
  PROTECTION FUNCTIONS

ANSI Protection Functions We Test & Calibrate

ANSI 50/51 Instantaneous & Time-Overcurrent Protection Verification of phase overcurrent pickup and IDMT curves (IEC Normal Inverse, Very Inverse, Extremely Inverse) to guarantee proper discrimination. Overcurrent (50/51)
ANSI 50N/51N Earth Fault & Sensitive Earth Fault (SEF) Testing ground fault detection thresholds and directional earth fault (67N) sensing for solidly grounded and resistance-grounded systems. Earth Fault (51N)
ANSI 87T/87G Transformer & Generator Differential Protection Restrained percentage differential testing, harmonic restraint (2nd & 5th harmonic blocking for inrush/overexcitation), and high-set instantaneous trip verification. Differential (87T)
ANSI 27/59 Under-Voltage & Over-Voltage Protection Voltage magnitude thresholds, drop-off timing, and neutral voltage displacement (59N) checks to protect motors and transformers from grid fluctuations. Voltage (27/59)
ANSI 32/40 Reverse Power & Loss of Field Protection Critical testing for captive generator synchronization panels to prevent generator motoring and loss of excitation damage. Generator Protection
03
  EQUIPMENT SUPPORT

Supported Numerical Relay Platforms

Manufacturer Supported Series Key Applications Testing Instrument
Schneider Electric MiCOM P12x, P14x, P64x, Sepam 20/40/80 Feeder, Transformer Differential, Motor OMICRON CMC 256
Siemens SIPROTEC 4 & 5 (7SJ, 7UT, 7SA series) Grid Substation Protection & Differential OMICRON CMC 256
ABB / Hitachi Relion 615, 630, 670 series (REF, RET, REM) Feeder, Transformer & Motor Management OMICRON CMC 256
SEL (Schweitzer) SEL-751, SEL-787, SEL-300 series Feeder Protection, Arc Flash Detection OMICRON CMC 256
04   RELAY TESTING FAQ

Frequently Asked Questions.

Expert answers regarding relay coordination and injection testing.

FREQUENCY How often should protection relays be tested?

Numerical relays should undergo secondary injection testing every 2 to 3 years. Electromechanical and static relays should be calibrated annually because spring tensions and internal electronic components drift over time.

COORDINATION Can TransfoLine help with relay coordination settings?

Yes. Our protection engineers perform full discrimination and relay coordination studies using ETAP/DigSILENT to calculate optimal pickup and time multiplier settings (TMS) before on-site injection testing.

06
  GET STARTED

Book Protection Relay Testing.

Our protection engineers deploy across Pakistan with calibrated OMICRON test sets.

Need secondary injection testing, nuisance trip investigation, or substation commissioning? Contact us directly.

Request Relay Testing Quote