The 100 kVA distribution transformer is Pakistan's most versatile commercial and light-industrial rating. Engineered for an operational full-load secondary current of 139.1 Amperes at 415V three-phase, this unit delivers high-efficiency power distribution for cold storage facilities, commercial retail plazas, poultry farms, fuel filling stations, and light manufacturing workshops across all DISCO utility networks.
Commercial pricing for a 100 kVA transformer in Pakistan is dictated by raw engineering commodities and technical configurations rather than an arbitrary sticker price. Here is how your commercial proposal is structured:
Prime 99.99% Electrolytic Copper provides maximum conductivity, lower I²R losses, and longer service life (25-30 years). EC Grade Aluminium windings provide a lower initial cost option for budget-sensitive seasonal agricultural projects.
Standard mineral oil-immersed (ONAN) with 210 Liters of Class-I inhibited oil is optimal for outdoor substations. Cast resin dry-type (AN/AF) is required for indoor commercial basements where fire regulations strictly prohibit oil.
Standard units include a 5-position Off-Circuit Tap Changer (OCTC: ±2.5%, ±5%) for seasonal grid adjustment. On-Load Tap Changers (OLTC) with automatic voltage regulating relays are available for sensitive manufacturing loads.
TransfoLine manufactures brand-new units (with 18-month guarantee) and supplies thoroughly overhauled certified reconditioned units (with 12-month replacement warranty) providing 40% to 50% capital expenditure savings.
A 100 kVA transformer in Pakistan varies in price based on conductor material (electrolytic copper vs. aluminium), condition grade (factory brand-new with 18-month warranty vs. certified reconditioned with 12-month warranty), tank construction (corrugated fins vs. tubular radiator), and whether turnkey civil plinth installation is included. For auxiliary or agricultural use, certified reconditioned units typically yield 40% to 50% savings over new units while maintaining complete WAPDA testing compliance.
Complete electrical, mechanical, and protection coordination data for electrical consulting engineers and DISCO inspection officers:
| Technical Parameter | Design Value / Rating | Standard & Engineering Notes |
|---|---|---|
| Nominal Power Rating | 100 kVA (80 kW (at 0.8 PF)) | Continuous maximum rating at 50°C ambient temperature |
| Primary High Voltage (HV) | 11,000 Volts (11 kV) | 3-Phase, 3-Wire delta configuration |
| Secondary Low Voltage (LV) | 415 Volts (Line-Line) / 240 Volts (Line-Neutral) | 3-Phase, 4-Wire star configuration with neutral bushing |
| Rated Secondary Current (LV) | 139.1 A | Continuous full load current at 415V secondary |
| Rated Primary Current (HV) | 5.25 A | Continuous full load current on 11 kV grid side |
| System Frequency | 50 Hz ±5% | WAPDA / NTDC National Grid synchronized |
| Vector Group | Dyn11 | Delta HV / Star LV with 30° phase lag neutral |
| Cooling Designation | ONAN (Oil Natural Air Natural) | Thermosiphon circulation through radiator panels |
| Percentage Impedance (%Z) | 4.0% | Guaranteed within ±10% IEC tolerance at 75°C reference |
| No-Load Losses (Iron Losses) | 260 Watts | Measured at rated voltage and frequency (CRGO core) |
| Full-Load Losses (Copper Losses) | 1,550 Watts | Measured at rated current at 75°C reference temperature |
| Transformer Mineral Oil Volume | 210 Liters | Uninhibited Class-I mineral oil (BDV > 50 kV fresh) |
| Total Weight (with Oil & Fittings) | 680 kg | Active copper winding weight: 165 kg |
| Overall Physical Dimensions | 1,100 mm (L) × 750 mm (W) × 1,250 mm (H) | Overall clearance footprint including radiators and conservator |
| Recommended HT Drop-Out Fuse Link | 6A / 10A Drop-Out Cutout Fuse Link | 11kV overhead cutout fuse link coordination |
| Recommended LT Main Circuit Breaker | 160A / 200A Molded Case Circuit Breaker (MCCB) | Thermal-magnetic or electronic trip unit coordination |
| Recommended Low Voltage Cabling | 3.5 Core 70mm² to 95mm² Cu / PVC / SWA Cable | Sized for <2.5% voltage drop at full load run |
| Civil Foundation Mounting | Pole-Mounted H-Frame or Ground Concrete Plinth | Under DISCO regulations (LESCO, FESCO, GEPCO, IESCO, MEPCO, PESCO, QESCO, K-Electric), a 100 kVA transformer requires B-2 (industrial) or C-1 (commercial) sanctioned load documentation. Pole-mounted structures require standard double-pole H-frame steel cross-arms with 11kV drop-out fuse cutouts and 9kV lightning arrestors. |
Real-world application engineering scenarios across Pakistani commercial facilities, textile mills, and agro-industrial clusters:
Supplies clean, regulated 415V/240V power to multi-story shopping plazas (10-18 commercial shops) operating heavy inverter air conditioning, commercial refrigeration, elevator lifts, and common area lighting without utility voltage drop.
Critical power source for modern broiler poultry sheds requiring uncompromised 24/7 ventilation fans, evaporative cooling pads, feed auger motors, and automated climate control systems in rural Punjab and Sindh.
Powers 25HP to 40HP semi-hermetic refrigeration compressors, blast chillers, and potato/onion cold storage warehouses across Gujranwala, Sialkot, Multan, and Okara agricultural belts.
Every TransfoLine 100 kVA transformer undergoes stringent factory routine testing before dispatch to ensure 100% first-time approval during DISCO departmental inspection:
Specify your factory or commercial plaza parameters. Our high-voltage estimation team will calculate your feeder requirements and deliver an itemized quotation within 2 business hours.
Direct engineering answers to frequently asked questions about purchasing, installing, and maintaining a 100 kVA transformer in Pakistan:
At standard 415 Volts three-phase line-to-line voltage, a 100 kVA transformer delivers approximately 139.1 Amperes of low-voltage (LV) full load current: 100,000 / (1.732 × 415) = 139.1 A. On the primary high-voltage (HV) side at 11,000 Volts (11 kV), the rated full load current is 5.25 Amperes.
For a rated current of 139.1A, an electrical engineer typically specifies a 160A or 200A Molded Case Circuit Breaker (MCCB) with adjustable thermal-magnetic or electronic trip units. This provides adequate protection against low-voltage overloads while allowing high motor starting inrush currents.
Yes. A 100 kVA transformer has an approximate total weight of 680 kg, making it fully suitable for standard WAPDA two-pole H-frame mounting using heavy-duty galvanized channel irons. It can also be installed on a ground-level concrete plinth if site space allows.
The price depends strictly on whether you require brand-new 99.99% copper windings (with 18-month warranty) or a certified reconditioned unit (with 12-month warranty), as well as current international copper rates and DISCO testing fees. Contact TransfoLine for an itemized commercial quotation based on current yard inventory.