The 2000 kVA (2 MVA) power transformer is an industrial heavyweight engineered for massive textile spinning and denim weaving mills (20,000+ spindles), large commercial shopping malls, continuous paper board manufacturing plants, and beverage bottling complexes in Pakistan. Delivering an immense 2,782.4 Amperes of low-voltage secondary current at 415V three-phase, this unit delivers high thermal stamina, robust short-circuit withstand capability, and low copper losses under continuous 24/7 heavy industrial operation.
Commercial pricing for a 2000 kVA (2 MVA Power Substation) transformer in Pakistan is dictated by raw engineering commodities and technical configurations rather than an arbitrary sticker price. Here is how your commercial proposal is structured:
Prime 99.99% Electrolytic Copper provides maximum conductivity, lower I²R losses, and longer service life (25-30 years). EC Grade Aluminium windings provide a lower initial cost option for budget-sensitive seasonal agricultural projects.
Standard mineral oil-immersed (ONAN) with 2,400 Liters of Class-I inhibited oil is optimal for outdoor substations. Cast resin dry-type (AN/AF) is required for indoor commercial basements where fire regulations strictly prohibit oil.
Standard units include a 5-position Off-Circuit Tap Changer (OCTC: ±2.5%, ±5%) for seasonal grid adjustment. On-Load Tap Changers (OLTC) with automatic voltage regulating relays are available for sensitive manufacturing loads.
TransfoLine manufactures brand-new units (with 18-month guarantee) and supplies thoroughly overhauled certified reconditioned units (with 12-month replacement warranty) providing 40% to 50% capital expenditure savings.
A 2000 kVA (2 MVA) power transformer represents a substantial capital investment for industrial facilities in Pakistan. Commercial pricing is governed by over 1,850 kg of pure 99.99% electrolytic copper, 2,400 liters of Class-I mineral oil, high-permeability laser-scribed CRGO core steel, and accredited high-voltage laboratory testing under WAPDA DDS-84 and IEC 60076. TransfoLine supplies brand-new 2 MVA units (18-month warranty) and certified reconditioned 2 MVA units (12-month warranty) with 40% to 50% capital savings and immediate dispatch from our Lahore yard.
Complete electrical, mechanical, and protection coordination data for electrical consulting engineers and DISCO inspection officers:
| Technical Parameter | Design Value / Rating | Standard & Engineering Notes |
|---|---|---|
| Nominal Power Rating | 2000 kVA (2 MVA Power Substation) (1,600 kW (at 0.8 PF)) | Continuous maximum rating at 50°C ambient temperature |
| Primary High Voltage (HV) | 11,000 Volts (11 kV) / 33 kV / 132 kV | 3-Phase, 3-Wire delta configuration (or customized) |
| Secondary Low Voltage (LV) | 415 Volts (Line-Line) / 240 Volts (Line-Neutral) | 3-Phase, 4-Wire star configuration with neutral bushing |
| Rated Secondary Current (LV) | 2,782.4 A | Continuous full load current at 415V secondary |
| Rated Primary Current (HV) | 105.0 A | Continuous full load current on 11 kV grid side |
| System Frequency | 50 Hz ±5% | WAPDA / NTDC National Grid synchronized |
| Vector Group | Dyn11 / YNd11 | Delta HV / Star LV with 30° phase lag neutral |
| Cooling Designation | ONAN / ONAF / OFWF | Thermosiphon circulation through radiator banks (forced cooling available) |
| Percentage Impedance (%Z) | 5.5% - 6.0% | Guaranteed within ±10% IEC tolerance at 75°C reference |
| No-Load Losses (Iron Losses) | 2,800 Watts | Measured at rated voltage and frequency (CRGO core) |
| Full-Load Losses (Copper Losses) | 18,000 Watts | Measured at rated current at 75°C reference temperature |
| Transformer Mineral Oil Volume | 2,400 Liters | Uninhibited Class-I mineral oil (BDV > 60 kV fresh) |
| Total Weight (with Oil & Fittings) | 6,800 kg (6.8 Tons) | Active copper winding weight: 1,850 kg |
| Overall Physical Dimensions | 2,650 mm (L) × 1,850 mm (W) × 2,650 mm (H) | Overall clearance footprint including radiators and conservator |
| Recommended HT Protection Switchgear | 11kV Vacuum Circuit Breaker (VCB) Panel with Numerical Relays | 11kV Vacuum Circuit Breaker with IDMT and Differential Relays |
| Recommended LT Main Circuit Breaker | 3200A 4-Pole Air Circuit Breaker (ACB) with LSIG Trip | Microprocessor-based electronic LSIG trip unit coordination |
| Recommended Low Voltage Cabling / Busway | Copper Busbar Trunking (BBT) or 6 Runs of 3.5 Core 300mm² Cu / XLPE | Copper Busbar Trunking (BBT) system sized for heavy current |
| Civil Foundation Mounting | Dedicated Outdoor Substation Bay with Heavy Reinforced Plinth & Oil Sump | A 2000 kVA (2 MVA) substation is classified under DISCO B-3 / B-4 industrial tariff. DISCO regulations (LESCO, FESCO, GEPCO, IESCO, MEPCO, KE) mandate a formal 11kV incoming Vacuum Circuit Breaker (VCB) panel with microprocessor overcurrent and earth-fault protection relays, dual copper grounding grids (<0.5 Ohm), safety interlocks, and a 3200A Air Circuit Breaker (ACB). |
Real-world application engineering scenarios across Pakistani manufacturing complexes, commercial hubs, and industrial zones:
Powers continuous ring frames, open-end rotor spinning machines, heavy sizing ranges, high-speed air-jet looms, and large industrial air washer compressor rooms in Faisalabad, Sheikhupura, and Nooriabad.
High starting torque support for large hydrapulpers, refiners, vacuum couch roll pumps, multi-cylinder paper drying drives, and calender stacks in Gujranwala and Kotri.
Serves as the central step-up substation transformer stepping up 415V/690V solar inverter output to 11kV for DISCO bidirectional net metering (NEPRA B-3/B-4 regulations).
Every TransfoLine 2000 kVA (2 MVA Power Substation) transformer undergoes stringent factory routine testing before dispatch to ensure 100% first-time approval during DISCO departmental inspection:
Specify your factory or substation parameters. Our high-voltage estimation team will calculate your feeder requirements and deliver an itemized quotation within 2 business hours.
Direct engineering answers to frequently asked questions about purchasing, installing, and maintaining a 2000 kVA (2 MVA Power Substation) transformer in Pakistan:
At standard 415V three-phase line-to-line, a 2000 kVA (2 MVA) transformer produces 2,782.4 Amperes of low-voltage (LV) full load current: 2,000,000 / (1.732 × 415) = 2,782.4 A. On the 11 kV primary high-voltage side, the rated full load current is 105.0 Amperes.
A 3200A 4-Pole Air Circuit Breaker (ACB) with a microprocessor-based trip unit providing adjustable Long-time, Short-time, Instantaneous, and Ground-fault (LSIG) protection is the standard engineering specification. Low-voltage distribution is typically handled via a copper Busbar Trunking (BBT) system or 6 parallel runs of 3.5-core 300mm² XLPE copper cables.
A 2000 kVA transformer weighs approximately 6,800 kg (6.8 metric tons). It requires a heavy reinforced concrete foundation plinth (minimum 3000 psi concrete) measuring at least 3,200 mm × 2,400 mm × 450 mm deep, surrounded by an oil-soak gravel pit capable of containing 100% of the 2,400 liters of oil, enclosed by 2.2-meter security chain-link fencing.
A 600 kVAR to 750 kVAR automatic Power Factor Improvement (PFI) panel divided into 12 to 16 microprocessor-controlled capacitor stages with 7% detuned harmonic reactors is required to maintain plant power factor above 0.95.